Gdva-405 Advanced Automatic Current Transformer CT and Voltage Transformer PT Tester

GDVA-405 Advanced Automatic Current Transformer CT and Voltage Transformer PT Tester1.1 ApplicationTests for Current Transformer:» Excitation curve and parameters test» Turns ratio test» Ratio and phase error test» Polarity mark check» Winding resistance measurement» Secondary loop burden meas

Featured Products

GDVA-405 Advanced Automatic Current Transformer CT and Voltage Transformer PT Tester

1.1 Application

Tests for Current Transformer:
» Excitation curve and parameters test
» Turns ratio test
» Ratio and phase error test
» Polarity mark check
» Winding resistance measurement
» Secondary loop burden measurement
» Error line curve test for protection CT
» Transient CT parameters test
» CT nameplate guess
» Saturation hysteresis loop curve measurement

Tests for Voltage Transformer:
» Turns ratio test
» Ratio error and phase angle error test
» Polarity test
» Secondary burden test
» Winding resistance test

Applications of CT/PT Analyzer:
» CT nameplate check
» CT parameters check in work burden
» CT transient parameters analysis
» CT ratio and phase error calibration
» PT routine test


Specifications:
1Test standardsIEC60044-1, IEC60044-6, GB1208, GB16847, C57.13
2Power supplyAC220V±10%,50Hz/60Hz±10%
3Power output0.1~180V (AC)
4Current output0.001~5A(RMS)
5Power output300VA
6Max. knee voltage measurement45kv
7Current measurement range0~10A (automatically change range in 0.1/0.4/2/10A)
8Current measurement error<±0.1%+0.01%FS
9Voltage measurement range0~200 V (automatically change range in 1V/10V/70V/200V)
10Voltage measurement error< ±0.1%+0.01%FS
11Turns ratio measurement range1~35000;
1~2000 error<0.05%;
2000~5000 error>0.1%;
5000~35000 error<0.2%
12Phase measurementerror:±2min,resolution:0.01min
13Coil resistance measurementRange: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm)
Error< 0.2%RDG+0.02%FS
Maximum resolution: 0.1mΩ
14Temperature measurement-50~100 Celsius degree, error<3 Celsius degree
15CT Secondary burdenRange 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm)
Error <0.2%RDG+0.02%FS
Maximum resolution 0.001ohm
16PT Secondary burdenRange 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm)
Error <0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
17PT ratio measurementRange: 1~35000,
1~5000 error<0.2%
5000~35000 error<0.5%
18Saved data groups>1000groups
19Work conditionTemperature:-10ºC-50ºC, moist:≤90%
20Size485mm×356mm×183mm
21Weight<15Kg

Gdva-405 Advanced Automatic Current Transformer CT and Voltage Transformer PT Tester

Contact us