Lzck350-10 100/5A epoxy resin casting split iron core current transformer

LZCK350-10 100/5A Epoxy Resin Cast Split Core Current TransformerLZCK series resin split core current transformer is suitable forcurrent measurement and microcomputer protection of electrical equipment in 10KV and 35KV AC power system.It is widely used in compact fully insulated ring network switchgears such as ABB-Safe Ring/Saf

Featured Products

LZCK350-10 100/5A Epoxy Resin Cast Split Core Current Transformer
LZCK series resin split core current transformer is suitable forcurrent measurement and microcomputer protection of electrical equipment in 10KV and 35KV AC power system.It is widely used in compact fully insulated ring network switchgears such as ABB-Safe Ring/Safe plus...and cable distribution boxes.The transformer can be directly installed at the inlet andoutlet cables.The slice is imported silicon material. Thesemicircular ring core and secondary windings arevacuum poured by insulated resin.
Parameters
Technical parameters 
StandardsIEC60044-1; IEC 61869-2; NTC 2205; GB1208-2006
Rated primary current20-600A
Rated load≤25VA
Rated frequency50Hz or 60Hz
Rated secondary current5A or 1A
Rated short-me thermal current40kA, 1S
Rated connuous thermal current120%I1n
Secondary winding power-frequency voltage3kV, 1min
Instrument security factorFS ≤10
Mechanical parameters 
Dimensions (W×D×H) (mm)φ50xφ110x105
Weight (kg)3.1
Operang condions 
Operang temperature-35°C to +55°C
Daily average temp< +40°C
Altude<3500 meters
CondionNo existence of severely begrimed, erosive and radioacve gas in the air. Permission of long-term operaon under rated current.
Technical data
TypeLZCK350-10LZCK350-10LZCK350-10
PurposeMeasuring current transformerProtecon current transformerDouble winding current transformer
RaoAccuracy class and rated burden(VA)Accuracy class and rated load (VA)Composite accuracy class and rated load (VA)
I1/I20.51310P1510P1010P50.5110P1010P5
20/1  0.5  0.75    
30/1 0.51.5 0.751.25    
50/1 12 1.252    
75/122.53.751.2523 212
100/12.53.75522.5522.51.52.5
200/15  357.52.5 2 
300/110  357.53.75 2.5 
400/110  35105 2.5 
500/125  3.756.25105 2.5 
600/125  57.5107.5 5 
TypeLZCK350-10LZCK350-10LZCK350-10
PurposeMeasuring current transformerProtecon current transformerDouble winding current transformer
RaoAccuracy class and rated burden(VA)Accuracy class and rated load (VA)Composite accuracy class and rated load (VA)
600/125  57.5107.5 5 
50/5  2.5  2    
75/5  2.5  3    
100/52.5 3.75  5 2.5 2.5
200/57.5     2.55 2.5
300/510     5 22.5
400/515     7.5 2.55
500/525     7.5 2.55
600/530     10 37.5

Contact us